ASHRAE 90.1 Appendix G Baseline System Selection
SkillAI & modelsASHRAE 90.1 Appendix G baseline system selection criteria. Use when recommending HVAC system types, creating baseline models, or answering questions about ASHRAE 90.1 compliance.
Available today. Use it from your connected AI after setup.
No other account needed.
Connect ahel once, and every AI you use reads what you have installed.
Then ask your AI: use the ASHRAE 90.1 Appendix G Baseline System Selection skill
What this skill tells your AI
The instructions your AI receives, as published by natlabrockies/openstudio-mcp in .claude/skills/ashrae-baseline-guide/SKILL.md and read by ahel’s review.
System Selection (Table G3.1.1)
Select baseline system based on building type, heating fuel, and floor area / floor count.
Residential Buildings
(hotels/motels, dormitories, apartments)
| Heating Source | System |
|---|---|
| Fossil fuel / hybrid | System 1: PTAC (any size) |
| Electric resistance | System 2: PTHP (any size) |
Non-Residential Buildings
| Heating Source | < 25,000 ft2 | 25,000-150,000 ft2 | > 150,000 ft2 |
|---|---|---|---|
| Fossil fuel / hybrid (<=3 floors) | System 3: PSZ-AC | System 3: PSZ-AC | System 5: Pkg VAV w/ Reheat |
| Fossil fuel / hybrid (>3 floors) | System 3: PSZ-AC | System 5: Pkg VAV w/ Reheat | System 7: VAV w/ Reheat |
| Electric resistance (<=3 floors) | System 4: PSZ-HP | System 4: PSZ-HP | System 6: Pkg VAV w/ PFP |
| Electric resistance (>3 floors) | System 4: PSZ-HP | System 6: Pkg VAV w/ PFP | System 8: VAV w/ PFP |
Heated-Only Buildings
(warehouses, garages, no mechanical cooling)
| Heating Source | System |
|---|---|
| Fossil fuel / hybrid | System 9: Gas Unit Heater |
| Electric resistance | System 10: Electric Unit Heater |
System Summary
| # | Name | Equipment Level | Heating | Cooling | Plant Loops |
|---|---|---|---|---|---|
| 1 | PTAC | Zone | Electric resistance | DX single speed | None |
| 2 | PTHP | Zone | DX heat pump + elec backup | DX heat pump | None |
| 3 | PSZ-AC | Central (single zone) | Gas furnace or elec | DX single speed | None |
| 4 | PSZ-HP | Central (single zone) | DX HP + elec backup | DX heat pump | None |
| 5 | Pkg VAV w/ Reheat | Central (multi zone) | HW reheat coils | DX two speed | Hot water loop + boiler |
| 6 | Pkg VAV w/ PFP | Central (multi zone) | Electric PFP boxes | DX two speed | None |
| 7 | VAV w/ Reheat | Central (multi zone) | HW reheat coils | Chilled water | HW + CHW + condenser loops |
| 8 | VAV w/ PFP | Central (multi zone) | Electric PFP boxes | Chilled water | CHW + condenser loops |
| 9 | Gas Unit Heater | Zone | Gas unit heater | None | None |
| 10 | Electric Unit Heater | Zone | Electric unit heater | None | None |
Heating Fuel Logic
The heating_fuel parameter maps to:
"NaturalGas"→ fossil fuel systems (1, 3, 5, 7, 9)"Electricity"→ electric systems (2, 4, 6, 8, 10)"DistrictHeating"→ treated as fossil fuel path
Economizer Applicability
- Systems 3-8: Support air-side economizer (
economizer=Trueby default) - Systems 1-2, 9-10: Zone equipment, no economizer possible
- Climate zone affects economizer control type (not yet parameterized)
Multi-Zone Constraints
- Systems 1-2, 9-10: One unit per zone (zone equipment)
- Systems 3-4: One air loop per zone (PSZ = packaged single-zone)
- Systems 5-8: One air loop serves multiple zones (VAV)
When user provides multiple zones:
- Systems 3-4 create separate air loops per zone
- Systems 5-8 create one shared air loop
Tool Mapping
| Action | Tool | Key Parameters |
|---|---|---|
| Create baseline system | add_baseline_system | system_type, thermal_zone_names, heating_fuel |
| List available systems | list_baseline_systems | (none) |
| System details | get_baseline_system_info | system_type |
| Modern alternatives | add_doas_system, add_vrf_system, add_radiant_system | thermal_zone_names |
Two paths, know which you need: the tools above are generic wiring
templates (explicit topology control, no standards equipment efficiencies).
Use them to SELECT and WIRE a system type. For comparing systems or any
decision-grade EUI/comfort numbers, build each candidate through
openstudio-standards instead:
create_typical_building(system_type=..., hvac_only=True) — replaces only
the HVAC (standards-tuned), preserving loads/schedules/thermostats.
When to Recommend Modern Templates Instead
| Scenario | Recommendation |
|---|---|
| High ventilation requirements (labs, hospitals) | DOAS with fan coils or chilled beams |
| Many small zones with diverse loads | VRF heat pump system |
| Comfort-critical spaces, radiant heating/cooling | Radiant floor/ceiling |
| Net-zero or high-performance target | DOAS + Radiant or DOAS + VRF |