Foundation and ground heat transfer
SkillAI & modelsChoose and apply a ground heat transfer method, EPW ground temperatures for a fast approximate answer, or EnergyPlus Kiva for real slab-edge heat transfer. Use when a model has no ground temperatures, when slab or basement heat loss matters, or when the user asks about foundations, slabs, basements or crawlspaces.
Available today. Use it from your connected AI after setup.
No other account needed.
Connect ahel once, and every AI you use reads what you have installed.
Then ask your AI: use the Foundation and ground heat transfer skill
What this skill tells your AI
The instructions your AI receives, as published by natlabrockies/openstudio-mcp in .claude/skills/foundation-modeling/SKILL.md and read by ahel’s review.
Two methods, and they are not interchangeable. Pick deliberately.
set_ground_temperatures | set_kiva_foundation | |
|---|---|---|
| What it does | Writes the four Site:GroundTemperature:* objects from the EPW header | Solves a 2D finite-difference soil domain per floor |
| Needs from the user | Nothing | The foundation type, and ideally real insulation detail |
| Simulation cost | None | Substantial — one domain per floor |
| Good for | Screening runs, compliance work, models with no foundation information | Slab-edge loss, basement-dominated buildings, studying the foundation itself |
Default to the simple method. Reach for Kiva when the foundation is what the question is about,
or when the user asks for it. A Kiva surface ignores Site:GroundTemperature:BuildingSurface
entirely, so the two do not stack.
The simple method
1. set_ground_temperatures()
Resolves the EPW itself — the one import_gbxml used, or the model's own weather file. Writes
Shallow, Deep and FCfactorMethod from the EPW's measured values, and derives
BuildingSurface from the model's heating setpoints.
Why BuildingSurface is not written from the EPW: those are undisturbed soil temperatures, an
open field with no building on it. The EPW's own .stat file says they "should NOT BE USED in the
GroundTemperatures object to compute building floor losses". Boston's January figure is −0.29 °C;
writing that under a heated slab overstates the loss badly.
If the model has no thermostats yet, BuildingSurface is skipped with a reason — run it again after
HVAC, or state the value:
2. set_ground_temperatures(building_surface_method="constant", building_surface_constant_c=18.0)
The detailed method: Kiva
Always call get_foundation_options() first, then ask the user. Do not pick an archetype for
them.
1. get_foundation_options()
It reports which floors and below-grade walls EnergyPlus would accept, why each rejected surface was rejected, the exposed perimeter computed from the building footprint, how many Kiva domains would be created, and the five archetypes with their full parameter sets.
Put the choice to the user
Show them the archetype list with its actual numbers — not just the names. Ask which describes the building's foundation:
- Slab on grade, uninsulated
- Slab on grade with perimeter insulation
- Heated basement, insulated walls
- Unheated basement
- Vented crawlspace
Say plainly that the R-values are conventional starting points, not code-derived. There is no
vendored source for Kiva insulation geometry, so the archetype numbers are a way to skip a
ten-question interrogation, not a substitute for knowing the building. Each archetype carries a
basis string saying so, and the response reports the ASHRAE 90.1 F-factor / C-factor target for
the model's climate zone as a cross-check. If the user knows their real insulation, take it.
Apply it
2. set_kiva_foundation(archetype="heated_basement_insulated")
Overriding anything the user does know:
3. set_kiva_foundation(archetype="slab_on_grade_perimeter_insulated",
exterior_vertical_insulation_r_si=3.52,
exterior_vertical_insulation_depth_m=1.2)
Use dry_run=True to show the user exactly what would be written before committing:
4. set_kiva_foundation(archetype="unheated_basement", dry_run=True)
What to check in the result
provenanceon every value —user,archetype:<name>,epw_header,openstudio_default, orcomputed_geometry. Anything markedarchetype:*is a number nobody sourced; report that to the user rather than presenting the result as measured.ground_temperature_interaction— ifset_ground_temperaturesran earlier, this says which surfaces Kiva now governs and whetherBuildingSurfacestill applies to anything.warnings— unpaired below-grade walls, clamped interior bays, missing soil properties.
Expect refusals, and do not treat them as failures
EnergyPlus is strict about Kiva surfaces, and the tool refuses rather than writing a model that fails at run time:
- Massless construction layers are the most common blocker on a real Revit model. gbXML slabs
routinely carry no-mass layers and EnergyPlus refuses them outright. Fix with
create_standard_opaque_material,create_constructionandassign_construction_to_surface, then retry. This is normal, not an edge case. - Windows or doors on the surface — not allowed with a Foundation boundary condition.
- Walls with more than four vertices.
- Surfaces with no parent space.
- More than 20 eligible floors requires
confirm_many_domains=True, because that is 20 separate 2D domains and a much slower simulation.
Never set Foundation with set_surface_boundary_conditions — EnergyPlus also needs a
Foundation:Kiva object and an exposed-perimeter object, and fails fatally without them.
set_kiva_foundation writes all three together, and the other tool refuses the condition for that
reason.
After either method
Kiva needs a weather file at simulation time — EnergyPlus will not run it design-day-only. Neither
tool saves; call save_osm_model to persist.